Abstract
Objective To assess the flammability of five brands of dental procedure glove.
Design A total often gloves of each brand (Biogel-D, Premier Protectors, Roeko-D, Safeskin Satin Plus and Schottlander Low Allergy) underwent flammability testing. Five of these were tested as supplied (unwashed) and five following the application of the hand disinfectant Hydrex (washed). Each glove was stretched over a metal frame and the time to ignition, when exposed to a standardised butane flame, recorded. In addition, the thickness of each glove was also assessed by micrometer measurement.
Results All the gloves tested ignited in less than 2.5 seconds. Two way analysis of variance revealed significant effects of glove type (P< 0.001) and treatment (P< 0.05), together with a significant interaction of these factors (P< 0.05), upon the ignition time. Washing Roeko-D gloves with Hydrex significantly (P< 0.01) retarded the ignition time compared with those in the unwashed state. Both the glove thickness and material type appeared to be related to ignition time.
Conclusion The work presented here demonstrates the acute and varying flammability of a range of dental procedure gloves. It should serve as a reminder to those who routinely use open flames whilst gloved of the dangers of this practice.